DRY AUXILLARY DRUM-DRIP DRAINAGE PROCEDURES

The following procedure is to be followed:

ANNUALLY PRIOR TO FREEZING WEATHER, AND AS NEEDED DURING THE FREEZING SEASON

1) Close Number 1 Valve.

2) If present, remove plug from Number 2 Valve.

3) Ready a container large enough to handle the waste water (preferably a 5 gallon bucket).

4) Place container directly under valve outlet on Number 2 Valve.

5) Fully open Number 2 Valve and allow for complete draining.

6) Repeat steps 3 through 5 until no waste water is present.

7) After all waste water has been removed form drum-drip, close Number 2 Valve.

8) Replace plug.

9) Open Number 1 Valve.

10) The drainage procedure is now complete.